relais de contrôle de tension
voltage control relay

1. Applications
Used in single-phase control system, when the power supply is abnormal (voltage too high or too low), cut off the power to protect electrical equipment from damage.
2. Features
Built-in microprocessors, true RMS measurement, voltage measurement accuracy ≤1%. 50/60Hz universal, knob setting, LED indicator shows working status. Lock function with fault status, DIN rail mounting.
3. Technical parameters
Related control supply voltage: DC12V, AC/DC 24~48V, AC/DC 110~240V, AC220V 50/60Hz
Adjustable hysteresis value: 5~20% of threshold value
Fixed hysteresis value: 3% of threshold value
Action delay range: 0.1s~10s
Voltage measurement error: <1% (Entire setting range)
Delay error: ±10% +0.1s
Knob setting accuracy: 1% Scale value
Rated insulation voltage: 460V
Contact configuration capacity(A): 1 C/O: 8A
Utilisation category: AC-15
Contact capacity: Ue/le: 240V/1.5A
Electrical durability: 100,000
Mechanical durability: 1000,000
Degrees of protection: IP20
Pollution degree: III
Short circuit protector type: NT00-6A
Altitude: ≤ 2000m
Permissible relative humidity: ≤ 50% (40℃) No condensation
Installation: Screw mounting or DIN rail mounting
4. Function diagram

5. Wiring diagram

6. Dimension

Customization is acceptable, please contact us. Thanks!